Low Intensity CL0T/DL0T Cable
TYPE TC-CONTROL OR INSTRUMENTATION CABLE PVC/NYLONG INSULATION WITH OVERALL PVC JACKET
UL listed and OSHA acceptable. Recognized for use in Class l or 2, Division 2 hazardous locations and for installation in trays, wireways, troughs, channels, ducts and conduit. Specifically approved for direct burial, wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required. Designed for control, power, lighting, telemetering, signals and relay or traffic control.
Conductors
Bare soft annealed copper per ASTM B-3
Sizes 18 and 16 AWG (TFFN)
Bunch stranded. Size 18 (16/.010″) and Size 16
(19/.0117″)
UL-62 paragraph 10.2
Sizes 14, 12 and 10 AWG (THHN/THWN)
Concentric stranded, class B (7 strands)
ASTM B-8 and UL-83 table 13.l\
Insulation
High dieletric polyvinyl chloride
UL-1581 table 50.145 (THWN 75°C)
UL-1581 table 50.155 (THHN 90°C)
UL-1581 table 50.155 Class 12B (TFFN 90°C)
Thickness
UL-83 table 15.5 for THHN/THWN
UL-62 table 6.2 for TFFN
Nylon
UL-83 paragraph 25.l forTHHN/THWN
UL-62 paragraph 22.l forTFFN Thickness
UL-83 table 15.5 for THHN/THWN
UL-62 paragraph 26. 4 forTFFN
Overall Jacket
Gas/vapor-tight Polyvinyl Chloride (black)
UL1277 table 10.l
Thickness
specified herein
Color Coding
ICEA Method 3 Table K-2, except colors and numbers
are printed on solid base colors for easy identification.
Cable Identification
Sizes 18 and 16 AWG
Ink print on one side of jacket
“(size) AWG Type TC 90°C dry 75°C wet Sunlight Resistant
600V A.I.W. Corp. (UL) Direct Burial”
Indent print on other side of jacket “(number of conductors)”
Sizes 14, 12, and 10 AWG
Ink print on one side of jacket
“(size) AWG Type TC THHN or THWN cdrs. Sunlight Resistant
600VA.1.W. Corp. (UL) Direct Burial”
Indent print on other side of jacket “(number of conductors)”
Construction Options
Consult factory for cable specifications with appropriate shields.
Cables made per Dupont Spec. SE -33.4B also available.
This specification covers multiconductor cables having VW-1 TFFN or THHN/THWN (PVC/Nylon) conductors with an overall
gas/ vapor-tight polyvinyl chloride (PVC) jacket, conforming to Article 318 “Cable Trays” and Article 340 “Power and Control
Cable Type TC” of the 1996 National Electrical Code, and Standard 1277 of Underwriters Laboratories, Inc. Meets the
requirements of ICEA T-29-520 and T-30-520 flame tests as well as the 70,000 BTU “Cable Tray Propagation Test” per IEEE-383
and shows reserve capabilities by also pass the 210,000 BTU flame test. Rated 600 volts, 90°C dry and 75° wet. UL file no.
E60749. Also meets FT 4/IEEE 1202 70,000 BTU test.